Gleeds has been appointed for 3 Data Centers in Mumbai, all comprising of about 220,000 – 250,000 sq. ft space. The client does not subscribe to Uptime Institute Tiers and designs as per their requirements. Historically, their facilities are between Tier 3 and Tier 4.

Key Statistics

• Number of Server Floors – 3

• Parking – Single level

• Floor to Floor height – 7.5 to 8 Meters

• Number of Server Racks – 2560

• Cooling Per Rack – 10 KW 

• Total Critical Load – 19.2 MVA

• Total Critical Load + Flex – 25.6 MVA

• Number of Chillers – 17 Nos x 2000 TR each

• Number of Generator Sets – 25 Nos x 2480 Kw each

• Fuel Storage – Minimum 72 Hours